The Sanhua filter drier with replaceable cores (HTG series)
The Sanhua Filter Driers with replaceable cores (HTG series) are used in the liquid and gas lines of refrigeration, freezing and air conditioning systems with fluorine refrigerant gas.
These Filter Driers with replaceable cores are highly efficient in protecting refrigeration, freezing and air conditioning systems from moisture and other impurities.
The filter’s housing design allows you to select different types of cores. It’s sealed with a bottom cover for the ease of removal and replacement of the core from the bottom.
Sizes available:
1 core, ODM7/8 |
1 core, ODM1 1/8 |
1 core, ODM1 3/8 |
1 core, ODM1 5/8 |
1 core, ODM2 1/8 |
2 core, ODM1 1/8 |
2 core, ODM1 3/8 |
2 core, ODM1 5/8 |
2 core, ODM2 1/8 |
Burnout (Suction Line) |
DC-48 Core |
DM-48 |
|
INSTRUCTIONS for Sanhua Filter Driers Replaceable Cores |
Product Details
-
Key Features
- Highly efficient in moisture absorption, impurity, acid removal
- Corrosion resistant painting surviving 500 hour salt spray test
- Connection type: Copper or steel tube solder
- SH-48A filter element
- Applicable refrigerant: R22, R134a, R404A and R407C
- Applicable hybrid refrigerant: R124, R125, R134a, R143a, R152a, R218, R23 and R32
- Great desiccation ability is applicable under wide range of temperatures showing high pressure educability and excellent anti-shock performance. The even size of desiccant beads removes impurities effectively and keeps low pressure drop.
- Composition of solid element: 3A Desiccant, active alumina for acid absorption.
- SH-48Hfilter element
- Great water absorption performance, effectively filter out impurities 100% 3A desiccant. Can work with POE oil with strong moisture absorption capability.
- Applicable refrigerant: R134a, R 404a and R 407C etc.
- SH-48C filter element
- Great desiccation ability is applicable under wide range of temperature showing high pressure educability and excellent anti-shock performance. The even size of desiccant beads removes impurities effectively and keep low pressure drop.
- Protecting compressor, the drier core effectively absorbs acid and water; filters out impurities; extends the service life of compressor.
- Applicable refrigerant: R22, R134a, R404A and R507
Corrosion resistant painting surviving 500 hour salt spray test
Highly efficient in moisture absorption, impurity, acid removal
Highly efficient in moisture absorption, impurity, acid removal
Highly efficient in moisture absorption, impurity, acid removal
Specifications | |
---|---|
Applicable refrigerant | HCFC, HFC and CFCx |
Applicable medium temperature | 50°C ~ +120°C |
Applicable ambient temperature | -50°C ~ +80°C |
Maximum working pressure | HTG-A48: PB = 35 bar, HTG-A96: PB = 35 bar, HTG-B44: PB = 35 bar, HTG-B92: PB = 28 bar |
PED |