• +64 9 361 4060
  • NZ
  • MVR 300 Refrigerant Leak Detector

    Refrigerant Detector for Systems in Occupied Spaces.

    The MVR-300™ detector is specifically designed to provide continuous monitoring for refrigerants associated with high-efficiency, high volume refrigerant cooling and heating systems, such as VRF/VRV (Variable Refrigerant Flow/Variable Refrigerant Volume) systems. Typical applications include hotels, dormitories, hospitals, office buildings, and apartment buildings.

    The MVR-300™ audible and visual alarms alert occupants and simultaneously communicate to Building Management Systems/Building Automation Systems (BMS/BAS). Two on-board relays can be used to close valves, activate alarm devices and exhaust fans or initiate emergency calls to rescue teams.

    The on-board Modbus RTU interface provides real-time information about concentrations, status and settings. It also enables custom configuration of the MVR-300™ to any application specific requirements using multiple Modbus registers.

    The MVR-300™ is designed for easy installation and simple maintenance.

    IMPORTANT NOTE: Large refrigerant leaks into occupied spaces can reach concentrations that pose a suffocation risk to the occupants. The MVR-300™ is not designed to be used as the sole safety device for this risk. Safety of the occupants also must take a system designed approach that includes things such as ventilation, detection, early warning, mitigation and design redundancy.

    Delivery Information

    All deliveries are despatched from our Auckland warehouse.

    Orders placed before 10am will be picked for despatch same day.

    Orders placed after 10am will be picked for despatch the following day.

    Delivery times are subject to location, with standard service being:

    Auckland: Next Day Delivery.

    North Island (Main Centres): Next Day Delivery.

    South Island (Main Centres): Delivery 2 days Following Despatch.

    Pricing & Orders
    • For pricing and orders please contact us.
    • This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

    Product Details

    Specifications
    Detectable Gases R-410A, R-407C, R-404A, R-32
    Measuring Ranges 2,500 ppm, 5,000 ppm, 10,000 ppm
    Housing Flush mount, white ABS, fits in most 2-gang electrical back-boxes
    Size (L x W x D, approx.) 6" x 4.1" x 1.75" (150 x 105 x 45 mm) including bezel
    Protection Indoor: IP40, NEMA 1
    Weight (approx.) 8 oz (230 g)
    Power 100 to 240 VAC, 50/60 Hz, 4 W max.
    Indicator Tri-color LED: green, amber, red
    Buzzer 80 dB at 12" (30 cm)
    Relay Two SPDT: low alarm and high alarm / fault, normal or fail-safe; configurable
    Relay Rating 1 A at 30 VDC; 1A at 125 and 250 VAC, resistive load
    Alarm Delay 0 to 15 minutes; configurable 0, 5, 10, 15
    Wiring Power: 3-core cable, 14 to 20 AWG (0.5 to 2.0 mm2)
    Relay: 3-core cable, 18 to 20 AWG (0.5 to 1.0 mm2)
    Modbus: 2-core twisted pair shielded cable 18 to 24 AWG
    Modbus RTU Baud Rage: 9,600 or 19,200; configurable
    Environmental Conditions Operating Temperature: 32 to 120°F (0 to 50°C)
    Storage Temperature: 5 to 100°F (-20 to 40°C)
    Humidity: 5 to 90% RH, non-condensing
    Pressure: 23.6 to 32.5 inch of Hg (800 to 1,100 hPa)
    Elevation 0 to 6,560 ft. (2,000 m) altitude
    Sensor life 2 year minimum life with recommended 6 month testing and/or recalibration
    Approvals CE, UL/CSA/IEC/EN 61010-1