Multi-Zone Refrigerant Monitor
Bacharach’s Multi-Zone Refrigerant Monitor provides precise measurements of low-level refrigerants and naturals carbon dioxide and ammonia.
The continuous monitoring of ammonia, CO2 and synthetic refrigerant gas provides fast and early refrigerant leak detection, ensuring compliance with refrigeration safety standards and emission regulations.
Bacharach’s Multi-Zone Refrigerant Monitor delivers the best refrigerant leak detection available, with industry-leading MDL of 1ppm for halogenated gases, the fastest sampling frequency and the widest range of refrigerants accurately detected.
The large graphic LCD display and LED status indicators provide a system-wide overview at a glance.
The Multi-Zone enhances effective refrigerant management and ensures compliance with refrigeration safety standards (ASHRAE 15, EN 378, CSA-B52) and emissions regulations (F-Gas, CARB RMP).
It detects leaks early to enable cost savings by reducing refrigerant recharge, enhancing energy efficiency and reducing risk of refrigeration failure and produce loss.
A variety of communication interfaces are available including Modbus, BACnet and LonWorks, allowing easy integration into BMS / BAS systems and remote monitoring solutions.
Infra-red sensor technology provides accurate measurements of low ppm levels and is unaffected by other gases, humidity and temperatures.
Accurately detects leaks in up to 16 separate areas, which can expand to 48 monitoring points, ideal for grocery store refrigerant monitoring.
Overview Gas Leak Detection Systems
Tech Tips | Diagnosing Flow Faults in the MZ Monitor
Product Details
-
Key Features
- • Industry-leading 1 ppm Minimum Detectable Level (MDL) for refrigerants
- • Gas library contains 60+ refrigerants, including CFCs, HFCs, HCFCs, HFOs and natural refrigerants (R-744, R-717)
- • Identify leaks early to mitigate refrigerant loss, protect produce, enhance energy efficiency
- • Capable of monitoring up-to 16 zones (expandable up to 48 sample points) and detecting multiple gases with a single monitor
- • Minimal maintenance and no calibration required
- • High performance sampling pump
- • Halogen, CO2 and NH3 versions available
Specifications | |
---|---|
Sensor Channels | 4 to 16 point sampling system using IR sensor technology |
Sample Points | 48 |
Gases | Refrigerants: CFCs, HFCs, HCFCs, HFOs |
Natural Refrigerants: Ammonia, Carbon Dioxide | |
Measuring Range * | Refrigerants 0 to 10,000 ppmValue |
Ammonia 25 to 10,000 ppmValue | |
Carbon Dioxide 300 to 8,000 ppm | |
Sensitivity / Minimum Detection Limit * | Refrigerants 1 ppm |
Ammonia 25 ppm | |
Carbon Dioxide 10 ppm | |
Accuracy | ±1 ppm ±10% from 0-1000 ppm (refrigerants) |
±10 ppm ±10% from 0-10,000 ppm (Ammonia) | |
±5 PPM ±5% from 300-1000 ppm (CO2) | |
Sampling Distance | 0 to 1,200 ft. (0 to 365 m) for each sampling point |
Display | Backlit, graphic LCD 160 x 128 pixel; three status LEDs |
Output | |
Digital | Modbus® RTU via RS 485 |
Analog | 4 to 20 mA (optional) |
Power Supply | 100 to 240 VAC, 50 / 60 Hz |
Relay | 3 alarm relays, 1 fault relay, SPDT |
Rating 5 A @ 250 VAC, resistive load | |
Ambient Conditions | |
Temperature | 32 to +122 °F (0 to +50 °C) |
Humidity | 5 to 90 %RH, non condensing |
Altitude | 0 to 6,560 ft (2,000 m) |
Enclosure | Powder-coated aluminum |
Size (L x W x H) | Approx. 13.7” x 12.3” x 5” (350 x 315 x 130 mm) |
Weight | Approx. 15 lbs. (6.8 kg) |
Approvals | CE, UL, CSA, EN 61010-1, EN 61326, EN 14624 |
Sensor Type | NDIR |
Expected Sensor Service Life | 10 Years |
* See data sheet for details |